BFI-P2-34-0240-3F4A-MN

Article number 60422

  • Output power 11 kW
  • Output 3×400 VAC, 24 A
  • Input voltage 3×380-480 VAC
  • IP66

Facts

General description

Article number 60422
Warranty 2 year

Mechanical

IP class IP66
Physical size Size 3
Measurements (H x W x D) 310 mm x 211 mm x 266 mm
Weight 7,1 kg
Typical power loss at rated power 2 % of rated power
Main switch No
Built in Main switch, control switch and potentiometer No
Conformal coated PCBs Yes, IEC 60721-3-3, 3S3/3C3

Output ratings

Output voltage 3 x 400 VAC
Rated motor current 24 A
Overload capacity 150% for 60 seconds, 200% for 4 seconds
Motor power 11 kW
Output frequency 0 – 500Hz, 0.1Hz resolution
Supported motor types 3 phase AC induction (IM), AC permanent magnet (PM), Brushless DC (BLDC), Synchronous reluctance (SynRM)
Built-in brake transistor Yes
Regenerative capacity 100 % ED

Input ratings

Supply voltage 380 – 480VAC ± 10%
Voltage fluctuations +/- 10%
Phase imbalance 3% maximum allowed
Displacement factor > 0.98
Supply frequency 48 – 62Hz
Power cycles 120 per hour maximum, evenly spaced

Control specification

Control modes V/F Voltage Vector, Energy Optimised V/F, Sensorless Vector Speed Control, Sensorless Vector Torque Control, Synchronous Reluctance Motor Control, Brushless DC Motor Control, Closed Loop (Encoder) Speed Control, Closed Loop (Encoder) Torque Control, Open Loop PM Vector Control
Current/torque limitation Torque and current limitation
PWM frquency 4-32 kHz effective
Stopping mode Ramp to Stop: User Adjustable 0.01 – 600 seconds, Fast stop, Coast to Stop
Braking Motor Flux Braking, Built-in Braking Transistor
Skip frequency Yes
Analog setpoint control 0 to 10V, 10 to 0V, −10 to 10V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA
Digital setpoint control 8 fixed speeds, Motorised Potentiometer, Internal PLC, Keypad, Modbus RTU, CANopen, Optional: PROFIBUS DP, DeviceNet, EtherNet/IP, EtherCat, PROFINET, Modbus TCP, CC-Link

Communication

Modbus RTU Yes, 9.6 – 115.2 kbps (8N1, 8N2, 8E1, 8O1)
BACnet MS/TP No
Modbus TCP Yes, external option
Ethernet IP Yes, external option
EtherCat Yes, external option
Profinet IO Yes, external option
Profibus DP(DPV1) Yes, external option
Device Net Yes, external option
CC-Link Yes, external option
CAN open Yes, 125-1000 kbps

Display

Programmable display Yes
Multi language OLED display TFT Display
External OLED display Yes, TFT Display
LED display No

HVAC

PID-control Yes with sleep/wake up functionality
Spin start Yes
Pump dry protection No
Pump prime and burst protection No
Stir function No
Motor pre-heat No
Broken impeller and broken belt detection No
Automatic cleaning for pumps No
Bypass control Yes
Fire mode No

Control terminals

Power supply 100 mA @ 24 VDC, 20 mA @ 10 VDC
Inputs 5 in total, 3 Digital, 2 Analog or Digital, selectable
Digital inputs 10-30 V DC, PNP, Response time: < 4 msec, Internal or external supply
Analog inputs Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling
Outputs 4 total, 2 relays, 2 analog or digital
Digital transistor outputs 24VDC/20 mA, Internal supply
Relay outputs Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 5A AC, 5A DC
Analog outputs 0 to 10 Volt, 0 to 20mA, 4 to 20mA
Safety inputs 2
Extra IOs Yes, internal option

Control features

Speed control Master/slave Yes, Master and slave
Modbus master functionality Yes, Master and slave
Advanced hoist control Yes
Built-in PLC Yes

Standard compliances

Low voltage directive 2014/35/EU
EMC directive 2014/30/EU
Conformance CE, UL, cUL
Machine directive 2006/42/EC
Marine approvals No
Safe torque OFF Cat 3/PL”d” According to ISO 13849-1, SIL CL 2 According to EN61800-5-2 / EN62061 / IEC61508
Restriction of hazardous substances RoHS2
Registration evaluation and authorisation of chemicals Reach
Earth leakage current EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1×230 VA < 2,5 mA, 3x400VAC < 4,65 during runing
DC Bus discharge time EN 61800-5-1:2007
Electrostatic discharge EN 61800-3:2004+A1-2012. Test techniques EN 61000-4-2:2009.
Dielectric strength 61800-5-1: 2007
Surge EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006.
Electrical fast transient burst EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-4:2004.

Ambient conditions

Temperature operation -10 to 40 °C
Humidity 95% max, non-condensing

Maintenance

Fault memory Last 4 Trips stored with time stamp
Data logging Logging of data prior to trip, Current, Temperature, DC Bus Voltage
Maintenence indicator Yes. Onboard service life monitoring
Monitoring Hours Run Meter, kWh/MWh meter


Smart Engineering Resources

Resources

Knowledge

Drawings

Certificates

Data sheets

Brochures

Program examples/Start-up

Manuals

Software

Configuration files