GT-3704
Analog input
- 4 channels
- PT100 / PT1000 / Ni1000LG / etc,
- 16bit resolution
- 10pt removable terminal block
Facts
General description
Article number | 100-8040 |
Warranty | 2 year |
Article status | Active |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistence | Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test |
Industrial emissions | EN 61000-6-4/A11: 2011 |
Industrial immunity | EN 61000-6-2:2005 |
Horisontal, Vertical | |
Product certifications | CE, UL, FCC, RoHS, China RoHS, Reach |
Power dissipation | Max. 130mA @ 5VDC, 0mA @ 24VDC |
Isolation | I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation |
Field power | Not used. Field power bypassed to next expansion module. |
Weight | 60g |
Module size | 12x99x70mm |
Environmental
Mounting | 35mm DIN rail |
Operating temperature | -40 ~ 70℃, Degraded performance > 60℃ |
Storage temperature | -40 ~ 85℃ |
UL temperature | -20 ~ 60℃ |
Relative humidity | 5 ~ 90% non-condensing |
Analog input module specifications
Calibration | Not required |
Connection types | 3-Wire |
Conversion time | ≤ 150ms, all channels |
Data format | 16bit integer (2´s complement) |
Exitation current | About 1mA |
Indicators | 4 green input status |
Inputs per module | 4 channels |
Module accuracy | PT1000: ±0.5℃ Full Scale @ 25℃ ambient, PPT1000: ±0.1℃ Full Scale @ 25℃ ambient, PPT1000: ±0.3℃ Full Scale @ -40,70℃ ambient, Cu10: ±2% Full Scale @ 25℃ ambient, Cu10: ±4% Full Scale @ -40,70℃ ambient, Cu100: ±0.3% Full Scale @ 25℃ ambient, Cu100: ±0.5% Full Scale @ -40,70℃ ambient, ±0.1% Full Scale @ 25℃ ambient, ±0.3% Full Scale @ -40,70℃ ambient |
Resolution in ranges | RTD Type: ±0.1℃/ F , Resistance type: 100 / 10 / 20 / 50mΩ |
Sensor types | RTD Input, , PPT1000 (PT1000 Precise Mode): 50~150°C, Cu10,Cu100: 100~260°C, PT100, PT200, PT500, PT50: 200~850°C, PT1000: 200~350°C, JPT100, JPT200, JPT500, JPT50: -200~640°C, JPT1000: -200~350°C, NI100, NI200, NI500: -60~250°C, NI1000: -60~180°C, NI120: -80~260°C, NI1000LG: -50~120°C, , Resistance Input, , 100mΩ/bit: 0~2000Ω, 10mΩ/bit: 0~327Ω, 20mΩ/bit: 0~620Ω, 50mΩ/bit: 0~1200Ω |