GT-4114
Analog output
- 4 analog outputs
- 0~20mA
- 12bit resolution
- 10pt removable terminal block
Facts
General description
Article number | 100-8025 |
Warranty | 2 year |
Article status | Active |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistence | Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test |
Industrial emissions | EN 61000-6-4/A11: 2011 |
Industrial immunity | EN 61000-6-2: 2005 |
Horisontal, Vertical | |
Product certifications | CE, UL, FCC, RoHS, China RoHS, Reach |
Power dissipation | Max. 30mA @ 5VDC |
Isolation | I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation |
Field power | Nominal supply voltage: 24VDC, Voltage range: 60℃: 18~32VDC, 70℃: 18~26.4VDC |
Weight | 60g |
Module size | 12x99x70mm |
Environmental
Mounting | 35mm DIN rail |
Operating temperature | -40 ~ 70℃, Degraded performance > 60℃ |
Storage temperature | -40 ~ 85℃ |
UL temperature | -20 ~ 60℃ |
Relative humidity | 5 ~ 90% non-condensing |
Analog output module specifications
Calibration | Not required |
Common type | 4 channel / 4 common |
Conversion time | ≤0.15ms, all channels |
Data format | 16bit integer (2′ compliment) |
Diagnostics | Field Power OFF: LED BLINK, Field Power ON: LED OFF (no output), Field Power ON: LED ON (output) |
Indicators | 4 green output status LEDs |
Load resistance | Max. 250Ω |
Module error | ±0.1% full scale @ 25℃, ±0.3% full scale @ -40°C, 70℃ |
Output format | 0 ~ 20mA |
Outputs per module | 4 channel single end |
Resolution in ranges | 12bit: 4.88uA/bit |