GN-9289
Network adapter
- Modbus TCP slave / Ethernet/IP
- 2 x Ethernet 10/100Mbps
- Up to 63 expansion slices
- Built-in Ethernet switch
- 10pt removable terminal block
Facts
General description
Article number | 100-8015 |
Warranty | 2 year |
Article status | Active |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistence | Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test |
Industrial emissions | EN 61000-6-4/A11: 2011 |
Industrial immunity | EN 61000-6-2:2005 |
Horisontal, Vertical | |
Product certifications | CE, UL, FCC, RoHS, China RoHS, Reach |
System power | Nominal supply voltage: 24VDC, Voltage range: 60℃: 18~32VDC, 70℃: 18~26.4VDC, Output current limitation: 1.5A, Reverse polarity protection |
Power dissipation | Max. 70mA @ 24VDC |
Current for IO module | 1.5A @ 5VDC |
Isolation | System power to internal logic: Non-Isolation , System power I/O driver: Isolation |
Field power | Nominal supply voltage: 24VDC, Voltage range: 60℃: 18~32VDC, 70℃: 18~26.4VDC, * Field Power Range is different depending on IO Module series. Refer to IO Module`s Specification. |
Max current field power contact | DC 10A max |
Weight | 165g |
Module size | 54x99x70mm |
Communication
Station type | Slave |
Max expansion ports | 63 slices |
IO data size | Input 128bytes / Output 128bytes |
Max length bus line | 100 m |
Max network nodes | Limited by Ethernet Specification |
Baud rate | 100Mbps, Auto-negotiation, Full duplex |
Settable node address | IP-address |
Bus connection | 2 x RJ45 |
Other serial port | RS232 for MODBUS RTU |
Serial configuration | Node: 1 (Fixed), Baud Rate: 115200 (Fixed), Data bit: 8 (Fixed), Parity bit: No parity (Fixed), Stop bit: 1 (Fixed) |
Indicator | 6 LEDs, 1 Green/Red, Module Status (MOD), 1 Green, Physical Connection (DLINK), 1 Green, Exchange Data/Traffic Present (RUN/ERR), 1 Green/Red, Expansion I/O Module Statsus (IOS), 1 Green, System Power Status, 1 Green, Field Power Status, , 2 LEDs (each RJ45 Connector), 1 Yellow, Link/Active, 1 Green, Not used |
Module location | Starter module left side |
Field power detection | ~14VDC |
Environmental
Mounting | 35mm DIN rail |
Operating temperature | -40 ~ 70℃, Degraded performance > 60℃ |
Storage temperature | -40 ~ 85℃ |
UL temperature | -20 ~ 60℃ |
Relative humidity | 5 ~ 90% non-condensing |
Resources
Program examples/Start-up
- G series, GT-5112 Program example X2 Control and GN-9289
- G series, IP address, Subnet and Gateway Setting (KI00389)
- G Series, Nexto Xpress and GN-9289, Parameter Set of I/O modules
- G series, X2 Control, Parameter Set of I/O Modules connected to GN-9289 or GN-9273
- G series, X2 Control, Example with GN-9289
- Beijer GN-9289 with Allen Bradley RS Logix video tutorial
Software
- G series, BootP Server for IP-setting at GN-9372 and GN-9289
- IO Guide Pro Ver 1_2_0_3 for S- and G-series
- IOGuidePro V2.0.0.0 beta1
Firmware
Product information
Certificates
Knowledge
- G series, GN-9372, GN-9289 Default setting
- G series, Serial number, Production date
- Shock resistance of G- and M-series (IEC 60068-2-27)