BFI-H3-84-3700-3F12-MN
Article number 62587
- Output power 200 kW
- Output 3×400 VAC, 370 A
- Input voltage 3×380-480 VAC
- IP20
Facts
General description
Article number | 62587 |
Warranty | 2 year |
Mechanical
IP class | IP20 |
Physical size | Size 8 |
Measurements (H x W x D) | 974 mm x 444 mm x 423 mm |
Weight | 125 kg |
Typical power loss at rated power | 2 % of rated power |
Main switch | No |
Built in Main switch, control switch and potentiometer | No |
Conformal coated PCBs | Yes, IEC 60721-3-3, 3S2/3C2 |
Output ratings
Output voltage | 3 x 400 VAC |
Rated motor current | 370 A |
Overload capacity | 110% for 60 seconds, 150% for 15 seconds |
Motor power | 200 kW |
Output frequency | 0 – 250Hz, 0.1Hz resolution |
Supported motor types | 3 phase AC induction (IM), AC permanent magnet (PM), Brushless DC (BLDC), Synchronous reluctance (SynRM) |
Built-in brake transistor | No |
Regenerative capacity | No brake transistor |
Input ratings
Supply voltage | 380 – 480VAC ± 10% |
Voltage fluctuations | +/- 10% |
Phase imbalance | 3% maximum allowed |
Displacement factor | > 0.98 |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Total harmonic current distorsion | EN61000-3-12 |
Control specification
Control modes | V/F Voltage Vector, Energy Optimised V/F, Sensorless Vector Speed Control, Sensorless Vector Torque Control, Synchronous Reluctance Motor Control, Brushless DC Motor Control, Closed Loop (Encoder) Speed Control, Closed Loop (Encoder) Torque Control, Open Loop PM Vector Control |
Current/torque limitation | Torque and current limitation |
PWM frquency | 4-32 kHz effective |
Stopping mode | Ramp to Stop: User Adjustable 0.1 – 6000 seconds. Fast stop. Coast to Stop |
Braking | Motor Flux Braking |
Skip frequency | Yes |
Analog setpoint control | 0 to 10V, 10 to 0V, −10 to 10V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
Digital setpoint control | 8 fixed speeds, Motorised Potentiometer, Internal PLC, Keypad, Modbus RTU, BACnet, Optional: PROFIBUS DP, DeviceNet, EtherNet/IP, EtherCat, PROFINET, Modbus TCP, CC-Link |
Communication
Modbus RTU | Yes, 9.6 – 115.2 kbps (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | Built-in |
Modbus TCP | Yes, external option |
Ethernet IP | Yes, external option |
EtherCat | Yes, external option |
Profinet IO | Yes, external option |
Profibus DP(DPV1) | Yes, external option |
Device Net | Yes, external option |
CC-Link | Yes, external option |
CAN open | No |
Display
Programmable display | Yes |
Multi language OLED display | TFT Display |
External OLED display | Yes, TFT Display |
LED display | No |
HVAC
PID-control | Yes with sleep/wake up functionality |
Spin start | Yes |
Pump dry protection | Yes |
Pump prime and burst protection | Yes |
Stir function | Yes |
Motor pre-heat | Yes |
Broken impeller and broken belt detection | Yes |
Automatic cleaning for pumps | Yes |
Bypass control | Yes |
Fire mode | Yes |
Control terminals
Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
Inputs | 5 in total, 3 Digital, 2 Analog or Digital, selectable |
Digital inputs | 10-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Outputs | 4 total, 2 relays, 2 analog or digital |
Digital transistor outputs | 24VDC/20 mA, Internal supply |
Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 6A AC, 5A DC |
Analog outputs | 0 to 10 Volt, 0 to 20mA, 4 to 20mA |
Safety inputs | 2 |
Extra IOs | Yes, internal option |
Control features
Speed control Master/slave | Yes, Master and slave |
Modbus master functionality | Yes, Master and slave |
Advanced hoist control | No |
Built-in PLC | Yes |
Standard compliances
Low voltage directive | 2014/35/EU |
EMC directive | 2014/30/EU |
Conformance | CE, UL, cUL |
Machine directive | 2006/42/EC |
Marine approvals | No |
Safe torque OFF | Cat 3/PL”d” According to ISO 13849-1, SIL CL 2 According to EN61800-5-2 / EN62061 / IEC61508 |
Restriction of hazardous substances | RoHS2 |
Registration evaluation and authorisation of chemicals | Reach |
Harmonics | EN 61000-3-12 |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1×230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
DC Bus discharge time | EN 61800-5-1:2007 |
Electrostatic discharge | EN 61800-3:2004+A1-2012. Test techniques EN 61000-4-2:2009. |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Electrical fast transient burst | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-4:2004. |
Ambient conditions
Temperature operation | -10 to 50 °C |
Humidity | 95% max, non-condensing |
Maintenance
Fault memory | Last 4 Trips stored with time stamp |
Data logging | Logging of data prior to trip, Current, Temperature, DC Bus Voltage |
Maintenence indicator | Yes. Onboard service life monitoring |
Monitoring | Hours Run Meter, kWh/MWh meter |
Resources
Knowledge
- Alarm code running single phase motor with 3-phase output BFI
- Alarm, Excessive DC-rippel
- 24 VAC connected to terminal 1 will damaged the drive
- Input Phase Loss Detection
- Alarm O-I Instantaneous over current on drive output
- Alarm, INHIBIT
- Application Note BFI-H3, Fire Mode Operation
- Application Note BFI-H3, Bypass Operation
- Application note BFI-H3. Pump clean function
- Application note BFI-H3. Multi Pump Cascade control, DOL
- Application Note BFI-H3, Locking Parameters to Prevent Changes
- OLED Remote External Keypad, Working with Multiple Drive Networks
- Profibus contacts for BFI-P2 and BFI-H3
- Single phase motors run by BFI-E3/H3/P2
- DC-ripple
- Fans, external cooling fans
- Application Note BFI-H3, Optiflow Multi Pump Cascade Control
- Application Note BFI-H3, Setting the Motor Nameplate Details
- PID-control. Scaling of actual processvalue in display and unit
- BFI-H3, PID reference/setpoint from Fieldbus
- Modbus RTU and Modbus TCP communication at the same time
- Thermal protection inside motor connected to BFI-E3/P2/H3
- Emergency runing by a digital signal when normal running by Fieldbus/Ethernet
- Application Note BFI-H3, PID-control
- Application Note BFI-H3, Setting up Acceleration and Deceleration Ramp Rates
- Application Note BFI-H3, Setting the Required Stopping Mode
- CC-Link communication
- Forced manual control when runing Fieldbus control
- BFI cable connectors fork type
- BFI p2 e3 h3 hand control manual control
Drawings
- Cable CAB114: Cable for ModBus RS485 between Nexto Xpress and BFI
- Cable CAB113: Cable for ModBus RS485 between X2 panel and BFI
- CAD drawings: BFI-H3 IP66 (step and dwg)
- CAD drawings: BFI-H3 IP55 (step and dwg)
- CAD drawings: BFI-H3 IP20 (step and dwg)
- BFI connection into Modbus RTU or CANopen network
Certificates
- Manufacture Declaration for US and Canada
- Manufacturer declaration: BFI-H3 Declaration of Conformity CE
- Conflict Minerals Policy Statement
- Ecodesign for BFI Frequency Inverters
- Modern Slavery Act Company Statement
- RoHS 3, Restriction of Hazardous Substances. September 2021.
- REACH Directive Compliance Statement, September 2021
- Manufacturer declaration: BFI-H3 UKCA Declaration of Conformity
- Manufacturer declaration: UKCA Declaration of Conformity, Options for BFI
- Manufacturer declaration: CE Declaration of Conformity, Options for BFI
Data sheets
- Datasheet: Input AC Line chokes to BFI
- Datasheet: Sine wave filter
- Datasheet: Output chokes for BFI
- Datasheet: External EMC-filters for BFI
- Datablad Extern parameterenhet OPT-2-OPPAD-BFI
- Datablad Kablage för Modbus RTU mot BFI
- Specification of all BFI, Functions/Hardware
- Datasheet Isolator switch option for BFI-P2 IP55
- Datasheet Additional option board with 3 additional realy outputs
- Datasheet Additional option board with 3 digital inputs and one relay output
Brochures
Program examples/Start-up
- Program example BCS Tools and iX: Nexto communication with BFI by EtherCAT
- Program example iX Developer: Modbus TCP communication between any X2 and BFI-P2/H3.
- Program example iX Developer: Modbus RTU communication between any X2 and BFI-E3, BFI-P2 or BFI-H3.
- Program example CODESYS and iX: X2 Control communication with BFI-P2/BFI-H3 by Modbus TCP
- Program example CODESYS and iX: X2 Control communication with BFI by Modbus RTU
- Program example CODESYS and iX: X2 Control communication with BFI by EtherCat
- Program example BCS Tools and iX: Nexto Xpress communication with BFI by Modbus TCP
- Program example BCS Tools and iX: Nexto Xpress communication with BFI by Modbus RTU.
Manuals
- Manual Modbus RTU RS-485- communication
- Manual Profibus DP BFI-P2 and BFI-H3
- Manual BFI-Tools, PC-software for BFI
- Manual BFI-Smartstick for programming by Bluetooth
- Manual User Guide BFI-H3 (English) ver 3.08
- Kom-Igång dokument BFI-H3, Swedish
- Start-Up-Document Frequency Inverter BFI-H3 (KI00363D)